RN2-3~35KV high voltage fuse
Brand: lixiong
- Description
- Installation
- Inquiry
The RN2 type indoor high-voltage current limiting fuse is used for short-circuit protection of voltage transformers. Its current breaking capacity is 10002MVA. When short-circuiting, it can be instantly opened by limiting the line current to the minimum value. The fuse current should be in the range of 0.6~1.8A within 1 minute.
2. RN2-3~35KV high-voltage fuse_Technical data
Product model
|
RN2-3、6、10
|
RN2-15、20
|
RN2-35
|
|||
Rated voltage KV
|
3
|
6
|
10
|
15
|
20
|
35
|
Rated current A
|
0.5
|
|||||
Three-phase current shutdown capacity MVA
|
1000
|
|||||
Maximum switch-off current KA (Ratification value)
|
100
|
85
|
50
|
40
|
30
|
17
|
When the maximum short circuit current is turned off, the maximum current peak A
|
160
|
300
|
1000
|
350
|
850
|
700
|
Overvoltage multiple
|
No more than 2.5 times the working voltage
|
|||||
Melt tube resistance value
|
100±7
|
200±10
|
380±10
|
|||
Weight kg
|
5.6
|
12
|
15.6
|
|||
Melt tube weight kg
|
0.9
|
1.6
|
2.5
|
Request a Quote